Duct Size & CFM Calculator
A central system needs about 400 CFM of airflow per ton, and ducts sized to move it quietly. Enter your system size and duct role for the round diameter and rectangular equivalent.
Estimate only — a full ACCA Manual D design accounts for total run length and fittings.
How duct sizing works
Ducts are sized from airflow, not tonnage directly:
- Airflow first. A central AC moves roughly 400 CFM per ton (350 humid, 450 dry). A 3-ton system needs ~1,200 CFM.
- Then size for velocity. The cross-section is chosen so air moves at a target speed that is quiet without excess friction. This tool uses this site’s planning estimate of about 700 fpm in supply trunks and 500–600 fpm in branches and returns, then rounds up to the smallest standard round size that carries all of the airflow at or below that speed. Above 24″ it tells you to split the airflow.
- Too small raises velocity and static pressure: noisy vents, a strained blower, lost capacity. Too big wastes material and weakens the throw of air into the room.
For the whole picture — total run length, fittings and register selection — a full ACCA Manual D design is the standard.
Round vs rectangular duct
- Round ducts have the least friction for a given area and are the most efficient — use them where space allows.
- Rectangular ducts fit inside walls, joists and above ceilings, but need a larger cross-section than round to carry the same airflow. This tool gives the equal-friction rectangular equivalent for the height you pick.
Duct size by system (supply trunk)
Main-trunk sizes from the calculator above at 400 CFM/ton and this site’s planning target of about 700 fpm, rounded up to the smallest standard round size that carries all of the airflow at or below that speed:
| System | Airflow (CFM) | Exact size at 700 fpm | Round trunk |
|---|---|---|---|
| 1 ton | 400 | 10.2" | 12" |
| 1.5 ton | 600 | 12.5" | 14" |
| 2 ton | 800 | 14.5" | 16" |
| 2.5 ton | 1,000 | 16.2" | 18" |
| 3 ton | 1,200 | 17.7" | 18" |
| 4 ton | 1,600 | 20.5" | 22" |
| 5 ton | 2,000 | 22.9" | 24" |
Branch runs to individual rooms are smaller — commonly 6" for ~100 CFM, 7" for ~150, 8" for ~200.
CFM per ton and BTU ↔ CFM
Central air conditioners are commonly set up for about 400 CFM of airflow per ton (Carrier). ACCA notes that about 350 CFM per ton suits hot, humid climates, where slower air removes more moisture, and about 450 suits warmer, dry climates. The Bonneville Power Administration’s field-test program recommends 375–425 CFM per ton and treats 350 as the minimum. The equipment’s own airflow tables are the final word.
Sensible BTU/h = 1.08 × CFM × temperature change. The 1.08 is standard air (0.075 lb per cu ft) × its specific heat (0.24 BTU per lb·°F) × 60 minutes. Enter the measured difference between return and supply air. This counts sensible heat only, so it reads lower than the rated capacity, which also includes moisture removal.
| System | BTU/h | CFM at 350/ton | CFM at 400/ton | CFM at 450/ton |
|---|---|---|---|---|
| 1 ton | 12,000 | 350 | 400 | 450 |
| 1.5 ton | 18,000 | 525 | 600 | 675 |
| 2 ton | 24,000 | 700 | 800 | 900 |
| 2.5 ton | 30,000 | 875 | 1,000 | 1,125 |
| 3 ton | 36,000 | 1,050 | 1,200 | 1,350 |
| 3.5 ton | 42,000 | 1,225 | 1,400 | 1,575 |
| 4 ton | 48,000 | 1,400 | 1,600 | 1,800 |
| 5 ton | 60,000 | 1,750 | 2,000 | 2,250 |
Sources
- Carrier: What is CFM? — about 400 CFM per ton as a common target; e.g. a 3-ton unit about 1,200 CFM
- ACCA: 400 CFM per ton, or is it? — 350 CFM/ton suits hot-humid climates, 450 warmer-dry ones; use the manufacturer’s airflow tables
- Bonneville Power Administration: Airflow test detailed instructions — recommended 375–425 CFM per ton, minimum 350
Duct CFM chart: how much air each round duct carries
How many CFM a duct can carry depends on how much pressure you let it use up, called the friction rate (inches of water lost per 100 ft of straight duct). The chart shows three common friction rates. Which one fits your system is set by the blower’s available static pressure and the length of the longest run. That is the part a Manual D design works out, so this chart does not pick one for you.
| Round duct | CFM at 0.06 | CFM at 0.08 | CFM at 0.10 | Air speed at 0.08 |
|---|---|---|---|---|
| 4″ | 30 | 35 | 35 | 375 fpm |
| 5″ | 50 | 60 | 70 | 440 fpm |
| 6″ | 85 | 100 | 110 | 500 fpm |
| 7″ | 125 | 150 | 170 | 555 fpm |
| 8″ | 180 | 210 | 240 | 610 fpm |
| 9″ | 250 | 290 | 330 | 660 fpm |
| 10″ | 330 | 385 | 435 | 710 fpm |
| 12″ | 535 | 630 | 710 | 800 fpm |
| 14″ | 810 | 945 | 1,070 | 885 fpm |
| 16″ | 1,155 | 1,350 | 1,525 | 970 fpm |
| 18″ | 1,580 | 1,850 | 2,085 | 1,045 fpm |
| 20″ | 2,090 | 2,445 | 2,755 | 1,120 fpm |
Smooth round sheet-metal duct, straight runs, standard air at sea level, rounded to the nearest 5 CFM. Fittings (elbows, boots, takeoffs) add pressure loss on top. Flex duct carries less air than these figures, much less when it is compressed or sagging, so size flex from the manufacturer’s data.
Find the duct size for an airflow
—
How it is calculated: the Darcy–Weisbach equation, with the Colebrook equation for the friction factor. Inputs are standard air (68 °F, sea level) and a sheet-metal roughness of 0.09 mm for galvanized steel. At high altitude the air is thinner and the same duct carries slightly more CFM at the same friction rate.
FAQ
How many CFM per ton does an AC need?
About 400 CFM per ton is the common target (Carrier); ACCA puts the range at roughly 350 for hot-humid climates to 450 for warm-dry ones, and BPA's field program recommends 375–425 with 350 as the minimum. A 3-ton system needs about 1,200 CFM.
What size duct do I need for a 3-ton AC?
At this tool’s 700 fpm supply-trunk target, a 3-ton system (about 1,200 CFM) works out to an 18-inch round main trunk; use the calculator above for the equal-friction rectangular size at your duct height. Branch runs to individual rooms are much smaller, typically 6–8 inches.
Are round or rectangular ducts better?
Round ducts have the least friction for a given area and are the most efficient. Rectangular ducts fit inside walls and joists but need a larger cross-section to carry the same airflow.
Why does duct size matter?
Undersized ducts choke airflow, raise static pressure, get noisy and cut the system's capacity.
How do I convert BTU to CFM?
For equipment sizing, divide BTU/h by 12,000 to get tons, then multiply by the CFM per ton: 36,000 BTU/h ÷ 12,000 × 400 = 1,200 CFM. To find the heat an airflow actually moves, use sensible BTU/h = 1.08 × CFM × the air temperature change.
How do I convert CFM to BTU?
Sensible BTU/h = 1.08 × CFM × temperature change. For example, 1,200 CFM cooled by 20°F moves about 25,900 BTU/h of sensible heat. For sizing, CFM ÷ 400 × 12,000 gives the nominal BTU/h that airflow suits.
How much CFM can a 6 inch duct carry?
About 85–110 CFM in smooth round sheet-metal duct, at friction rates of 0.06 to 0.10 inches of water per 100 ft (about 100 at 0.08). Flex duct carries less, especially if it is compressed.
How much CFM can an 8 inch duct carry?
About 180–240 CFM in smooth round sheet-metal duct at 0.06 to 0.10 friction rate, or about 210 at 0.08.
What size duct do I need for 400 CFM?
A 12-inch round sheet-metal duct at a 0.08 friction rate (a 10-inch duct carries about 385 CFM, just under 400, so it rounds up). At 0.10 a 10-inch duct is enough. Use the duct size finder on this page for other airflows and friction rates.
Method & standards
Airflow is estimated at about 400 CFM per ton; duct sizes are computed for the selected role's target velocity, with the rectangular equivalent from the equal-friction diameter formula. This is a planning estimate — a full ACCA Manual D design accounts for total effective length, fittings and available static pressure.
Standards: ANSI/ACCA 1 Manual D — Residential Duct Systems (ACCA) and the ASHRAE Handbook — Fundamentals (ASHRAE). See our full methodology.
Updated 6 November 2026