Home / HVAC Load Calculator
Cooling + heating load · Multi-room · No signup

HVAC Load Calculator: Whole-House Cooling & Heating

Built by Murugan Vellaichamy, Sri Murugan Systems · sources checked November 2026 · how the numbers work

Add every room for the cooling load, then get the house’s heating load at your county’s winter design temperature below. Cooling: US mode recommends a central system size (or two or more equal systems above about 5.55 tons, where even a 5-ton unit would be under 90% of the load). India mode recommends a per-room split AC plan. Share your plan with a link, no account needed.

Climate & location
Rooms

Climate and tonnage snapping follow the US/India switch in the header. The share link encodes your rooms in the URL itself — nothing is uploaded.

Per-room results
Add rooms above.
Whole-house total
—TONS TOTAL
Total cooling load—
Duct airflow (nominal)—
Rooms—
Where the load comes from
Structure (area × climate) Ceiling · sun · roof People Windows
Recommendation

Whole-house heating load

The heating load is the heat the house loses on its design winter day. The heated area fills from your rooms above; pick your county for the official design temperature.

Location

Pick your county to fill the 99% heating design temperature from EPA’s ENERGY STAR reference guide, or type your own. Picking your county also sets its 2021 IECC climate zone (see the climate zone map).

Your home
Assumptions used (editable)

Design heating load
—BTU/H
At outdoor design temp—
Per sq ft—
Furnace output range—
Heating vs cooling load—
Size the equipment with the furnace calculator or the heat pump calculator — both use this same heat-loss method.
Part of the houseHeat loss at designShare

How to plan a whole-house system well

A whole-house estimate is only as good as the rooms you feed it. Four things to get right:

  • List every conditioned room. Include the ones you're tempted to skip — a central system cools the whole envelope whether you enter it or not.
  • Count occupants where people actually gather. Bedrooms and living areas, not an even spread across the floor plan.
  • Set sun exposure per room — don't average.
  • Mark top-floor rooms. This site’s planning estimate adds a roof factor for them.

What your total means

Whole-house totalRecommended setup
Up to about 5.55 tonsA single central system (5 tons is the largest, and it still covers at least 90% of a 5.55-ton load) — check the duct airflow (CFM) figure in the results above
Above about 5.55 tonsTwo or more equal systems — a residential central AC is rated below 65,000 BTU/h (10 CFR 430.2), so even a 5-ton unit would be under 90% of the load, and zoning one system adds no capacity
India modeA per-room split plan
Check the ductwork first. A new condenser is only as good as the ducts feeding it — a 3-ton system needs roughly 1,200 CFM. Old or undersized ducts that can't move the air will choke it, so verify the airflow figure the calculator shows before buying.

Next steps

  • No ducts? Plan the same rooms on the mini-split calculator.
  • Take it to a pro. Use the share link and PDF report to anchor the installer's quote.
  • Resist the round-up. The oversizing guide explains why bigger isn't safer at whole-house scale.

How the whole-house total is calculated

Each room is sized on its own load, then the rooms are summed:

  • Per room: floor area × climate BTU/sq ft × ceiling factor × sun factor (× roof factor if top-floor) + occupant heat.
  • House total: the sum of every room, converted to tons at 12,000 BTU/hr per ton.
  • Equipment: snapped to a standard size. The total is a plain sum of room loads; it does not apply diversity (an allowance for rooms peaking at different times).

US central vs India per-room

  • US mode assumes one central system cooling the whole envelope through ducts, sized to the combined load (or split into equal systems above about 5.55 tons).
  • India mode plans a separate split per room.

Switch with the US/India toggle in the header — the climate options and sizing rules change with it.

How the heat loss is calculated

Heat loss at the design temperature = (sum of each surface’s area × its U-factor + air leakage) × (70°F indoors − the outdoor design temperature). The 70°F indoor and the 99% outdoor design temperature are the conditions ENERGY STAR requires for HVAC design.

  • Design temperature: the county value from EPA’s ENERGY STAR Design Temperature Limit Reference Guide (2019 edition), which EPA compiled from ASHRAE and ACCA Manual J weather data. Where several weather stations fall within 40 miles of a county’s centre, EPA uses the coldest — so the value is on the safe side. A local jurisdiction’s own design temperature takes precedence.
  • Surfaces: the home is treated as a square box of the given floor area and stories, with windows as a share of wall area.
  • U-factors: the “new, 2021 IECC” option uses the code’s maximum U-factors for your climate zone. The other options are labelled assumptions, because no official values exist for existing homes; open “Assumptions used” to see or change them.
  • Air leakage: blower-door ACH50 converted to natural air changes with LBNL’s method (÷ about 19, adjusted for stories), then × 1.5 for design-day conditions (New York State Clean Heat guidance). The 2021 IECC limit is 3.0 ACH50 in zones 3–8 and 5.0 in zones 1–2.
  • Floor: floors over a crawlspace or unheated basement are taken to lose heat to outdoor temperature (conservative); slabs at half that rate (an assumption, since the ground is warmer than the air on a design day).

Not included: duct losses, internal gains and room-by-room effects. This is a whole-house planning estimate, not an ACCA Manual J calculation, which a contractor should run before buying.

FAQ

Is whole-house sizing just the sum of each room's calculator?

In this tool, yes: it totals the room loads and does not apply diversity (an allowance for rooms peaking at different times). Size the equipment on a contractor's Manual J load calculation. In India you don't diversify — each room gets its own split, so the per-room plan is the answer.

Should I install one large central AC or two smaller systems?

One system works up to about 5.55 tons, since a 5-ton unit still covers at least 90% of that load. Above that you need two or more equal systems: a residential central AC is defined as under 65,000 BTU/h (10 CFR 430.2), so 5 tons is the largest, and adding zone dampers to one system adds no capacity. The FAQ covers the one-vs-two decision in detail.

Which rooms should I include?

Every room a central system actually conditions — including ones you're tempted to skip, since the ducts cool the whole envelope regardless. Skip unconditioned garages, unfinished attics and crawlspaces unless you plan to cool them. Add appliance heat for kitchens.

Why does duct size matter when I upsize the AC?

A 3-ton system needs roughly 1,200 CFM of airflow; older or undersized ducts that can't move it will choke a new condenser, cutting capacity and efficiency. Verify the CFM figure the calculator shows against your existing returns and supplies before buying a bigger unit.

Is this a Manual J load calculation?

No. ACCA Manual J is the detailed room-by-room method contractors use, with every wall, window orientation and duct run. This calculator is a planning estimate built from the same principles: area, climate, sun and people for cooling, and envelope U-factors, air leakage and the county design temperature for heating. Use it to check a quote; ask the contractor for their Manual J before buying.

What is the difference between heating load and cooling load?

Cooling load is the heat that gets into the house on a hot design day (sun, people, outdoor heat); heating load is the heat the house loses on a cold design day. They are calculated differently and can lead to different equipment sizes, which is why a heat pump is checked against both.

What indoor temperatures are the loads based on?

70°F for heating and 75°F for cooling, the indoor design temperatures ENERGY STAR requires in its HVAC design report.

Heating sources

actonnagecalc.com is not affiliated with, or endorsed by, the U.S. EPA, ENERGY STAR®, DOE or the ICC. Their publications are cited as sources.

Method & standards

Per-room cooling loads are this site’s planning estimate (area × climate rate, with ceiling, sun and roof factors, plus occupants), not ACCA Manual J; US code requires a full Manual J before equipment selection — ACCA. See our full methodology.

Updated 6 November 2026