Home / AC Ampere Calculator
Electrical · MCB / breaker

AC Ampere Calculator & Breaker Rules

Built by Murugan Vellaichamy, Sri Murugan Systems · sources checked November 2026 · how the numbers work

Size the wire to the AC’s nameplate MCA (minimum circuit ampacity) and keep the breaker at or below its nameplate MOCP (max fuse/breaker). A 3-ton US condenser’s compressor is rated about 13.4–16 A (RLA) on makers’ spec sheets (about 4–6 A per ton); for an Indian split, take the MCB rating from the manufacturer’s installation manual. Use this for a planning estimate of running current; the nameplate figures govern.

Inputs

The amps shown are this site’s planning estimate of running current (4.8 A per ton, inside the compressor RLA ranges on makers’ spec sheets), not a nameplate value. A non-inverter compressor briefly draws its locked-rotor amps (LRA, printed on the nameplate) at start-up. Wiring decisions belong to a licensed electrician.

Reading the numbers like an electrician

The amps shown are a planning estimate of running current for the tonnage, not a figure to size a circuit from. The nameplate sets that: under NEC Article 440 the wire is sized to the MCA (125% of the compressor’s rated load amps plus the fan amps), and the breaker must not exceed the MOCP (“max fuse/breaker”). In India, use the MCB rating in the manufacturer’s installation manual.

Three things this tool leaves to a professional:

  • Wire gauge — length-dependent; our sister voltage-drop calculator covers the panel-to-condenser run.
  • Shared circuits — don’t. An AC gets a dedicated circuit, full stop.
  • Whole-panel capacity — use the panel selector below and the panel capacity guide.
Result
—AMPS

Running current, this site’s planning estimate

Makers’ RLA range—
Amps × volts—
Wire & breaker—
CircuitDedicated circuit required
Cross-check long cable runs with our sister tool voltdropcalc.com to keep voltage drop under 3%.

Breaker & circuit quick guide

Compressor running current (RLA) for US condensers, from makers’ spec sheets — always confirm against the nameplate MCA / MOCP. For Indian splits, use the MCB rating in the manufacturer’s installation manual:

SystemCompressor RLABreaker
3-ton condenser (US)13.4–16 ANo larger than the nameplate MOCP
4-ton condenser (US)18.5–19.9 ANo larger than the nameplate MOCP
Across sizesroughly 4–6 A per tonNo larger than the nameplate MOCP

Example: Carrier’s 3-ton 24ACC636 lists an MCA of 18.1 A and a 30 A maximum breaker. The data-plate MCA (minimum circuit ampacity) and MOCP (maximum overcurrent protection) are the authoritative sizing numbers.

US vs India wiring differences

  • US: central condensers run on 240 V double-pole breakers with a disconnect at the unit; sizing follows NEC Article 440 and the nameplate MOCP.
  • India: splits run on 230 V single-phase with a dedicated MCB, rated as the manufacturer’s installation manual specifies.

Running an AC on a generator?

A generator has to cover the compressor’s starting surge, not just the running amps shown here. Use backuppowercalc.com to size a generator for your AC and the rest of your backup load.

FAQ

What size breaker or MCB does my AC need?

Let the nameplate decide. Size the wire to the unit's MCA (minimum circuit ampacity: 125% of the compressor's rated load amps plus the fan amps) and keep the breaker at or below its MOCP (max fuse/breaker). Under NEC Article 440 the breaker for AC equipment can be larger than the wire's ampacity, so don't size one from the other. For example, Carrier's 3-ton 24ACC636 lists an MCA of 18.1 A and a 30 A maximum breaker. For an Indian split, use the MCB rating in the manufacturer's installation manual. A licensed electrician confirms.

Does an AC need its own dedicated circuit?

Yes. Central ACs and most splits need a dedicated circuit — sharing it with lights or sockets causes nuisance trips and is a code problem. Portable and small window units that plug into a wall outlet are the usual exception: one unit per outlet, as the unit's manual specifies.

Why is startup current so much higher than running current?

At start-up a non-inverter compressor briefly draws its locked-rotor amps (LRA), which are printed on the nameplate. The breaker is chosen from the nameplate MOCP, not from the running amps.

Can my 100 A panel take a new AC?

It depends on everything else already on the panel. The check is a load calculation under NEC Article 220, done by an electrician with the new unit's nameplate MCA. See the panel capacity guide.

Method & standards

breaker and circuit guidance follows NFPA 70 (NEC) Article 440 and IS 732; always confirm the nameplate MCA/MOCP — NFPA. See the wiring guide. See our full methodology.

Updated 6 November 2026