Home / Glossary
Glossary

HVAC & AC Sizing Glossary

Updated July 2026 · by Murugan Vellaichamy

Plain-English definitions of the 32 AC-sizing and HVAC terms used across this site — from tonnage and BTU to SEER2, ISEER, superheat and SACC. For the physics behind them, see how your AC works.

Sizing & load

AC ton (tonnage)

A unit of cooling rate, not weight: one ton = 12,000 BTU/hr (≈3.517 kW), historically the cooling from melting a ton of ice over a day. See the converter.

ACH (air changes per hour)

How many times a space’s full air volume leaks in and out per hour through the building envelope; higher ACH means a bigger infiltration load.

Block load

A load calculation treating the whole building as one zone. It sizes the equipment but says nothing about how much air each room needs.

BTU / BTU per hour

A British Thermal Unit is the heat needed to raise one pound of water by 1°F. Cooling capacity is quoted in BTU per hour.

Building envelope

The physical boundary between conditioned and unconditioned space: roof, exterior walls, windows, floor. Cooling load tracks envelope area, which is why BTU per square foot falls as buildings get larger.

Ceiling height correction

An adjustment for rooms taller than the standard assumed in a sizing chart, since load scales with volume rather than floor area. Indian rooms commonly need it because ceilings run higher than the US norm.

Cooling degree days (CDD)

A running total of how far and how long outdoor temperature sits above a base temperature over a season. Useful for estimating annual running cost, not for sizing.

Delta-T (temperature split)

The temperature drop across the indoor coil between return and supply air; about 8–11 °C (15–20 °F) is normal.

Design temperature

The outdoor temperature a system is sized to handle, taken from a percentile of local weather records rather than the record extreme. Sizing to the record high is the most common cause of oversizing.

Diversity factor

The assumption that not every room peaks at the same moment, applied when sizing a single system for many rooms. Without it, a multi-room system is sized on the sum of loads that never coincide.

Duct gain and duct loss

Cooling lost from ducts running through unconditioned space such as an attic. It can add 10-30% to the load a system must deliver.

Indoor design condition

The indoor temperature and humidity the load calculation targets, conventionally 75°F/50% RH in the US and 24-25°C in India. Lower targets raise the load sharply.

Infiltration

Unconditioned outside air leaking in through gaps in the envelope. On a leaky building it can account for a quarter of the cooling load.

Internal gain

Heat produced inside the space by people, lighting, appliances and equipment. In a server room it dominates the load entirely.

Latent capacity

The share of a system's output that removes moisture rather than lowering temperature. An oversized unit satisfies the thermostat before delivering its latent capacity, which is why the room ends up cold and clammy.

Latent heat / load

The energy needed to remove moisture from the air (dehumidification), as opposed to lowering temperature. See humidity & comfort.

Occupancy load

The sensible and latent heat given off by people, roughly 250 BTU/hr sensible per seated adult. Load calculations typically assume two occupants and add an allowance for each additional person.

Oversizing factor

Installed capacity divided by calculated load. Above roughly 1.25 the system starts short-cycling and dehumidifying poorly.

Part-load ratio

The fraction of rated capacity a system is actually delivering at a given moment. Single-stage equipment cannot run below 100%, so it cycles instead.

Peak load

The highest cooling load the space reaches, usually mid-afternoon on the design day. Equipment is sized to this, which is why it runs at part load almost all the time.

R-value & U-factor

R-value measures insulation’s resistance to heat flow (higher is better); U-factor is its reciprocal for a whole assembly like a window (lower is better).

Room-by-room load

A load calculation done per room, needed to size ducts and registers. Manual J produces both this and the block load.

Sensible heat / load

The energy needed to change air temperature, as opposed to latent (moisture) load.

Shading coefficient

How much solar heat a shading device blocks relative to unshaded glass. External shading beats internal blinds by a wide margin because it stops the heat before it enters.

SHGC (solar heat gain coefficient)

The fraction of solar heat a window lets through, from 0 to 1; lower blocks more sun.

SHR (sensible heat ratio)

The share of a system’s cooling that goes to lowering temperature versus removing moisture (sensible ÷ total).

Solar gain

Heat entering through glazing as sunlight. Orientation matters more than area: a west-facing window can contribute several times the gain of a north-facing one of the same size.

Square feet per ton

A rule of thumb dividing floor area by capacity, commonly quoted as 400-600 sq ft per ton. It ignores climate, insulation, glazing and occupancy, so it is a sanity check rather than a sizing method.

Thermal bridging

Heat bypassing insulation through a conductive path such as a steel stud or concrete slab edge. It makes the effective R-value of an assembly lower than the insulation's nominal rating.

Standards & codes

AHRI 210/240

The US industry standard that defines how SEER2, EER2 and HSPF2 are measured for residential AC and heat-pump equipment.

ASHRAE 55

The standard defining thermal comfort conditions, which is where indoor design temperature and humidity targets come from.

ASHRAE 62.1 / 62.2

The ventilation standards setting minimum outdoor air rates for commercial and residential buildings. Ventilation air is a load the equipment must carry.

ECBC

India's Energy Conservation Building Code, which sets envelope and equipment efficiency requirements for larger commercial buildings.

IECC climate zones

The US climate zone map underlying code requirements for insulation and equipment. Zone determines the design temperature a load calculation should use.

ISO 5151

The international test standard for non-ducted air conditioner performance, the basis for capacity ratings in markets including India.

Manual J / S / D

ACCA residential standards: Manual J calculates the load, Manual S selects equipment, Manual D designs the ducts. See Manual J explained.

National Building Code of India

The Indian code covering building services including ventilation and air conditioning provisions.

NEC Article 440

The US electrical code article covering air conditioning and refrigeration equipment, including how breaker and conductor sizes derive from nameplate values.

India specifics

AMC (annual maintenance contract)

A yearly service agreement covering scheduled cleaning and sometimes parts. Comprehensive contracts include gas and components; basic ones cover labour only.

BEE star rating

India’s Bureau of Energy Efficiency 1–5 star label for room ACs, based on ISEER. See the star rating guide.

Copper vs aluminium coil

Copper coils resist corrosion and are easier to repair; aluminium is cheaper and lighter. In coastal and polluted areas the difference in service life is substantial.

Installation kit

The copper piping, drain pipe, wiring and brackets supplied or bought separately when a split is installed. Standard kits assume a short pipe run; longer runs cost extra and need a charge check.

ISEER

Indian Seasonal Energy Efficiency Ratio — the BEE metric behind India’s star ratings, tested across 24–43 °C.

Monsoon latent load

The moisture load during the monsoon, when outdoor humidity is high but temperature is moderate. Sensible cooling drops while moisture removal matters more, which is when oversized units feel worst.

RCC roof heat

The heat load from a reinforced concrete roof under direct sun, which makes top-floor rooms markedly harder to cool than the same room on a middle floor.

Star label validity

Indian BEE star thresholds tighten periodically, so a unit's star rating is tied to a label period. A 5-star model from an earlier period may only meet a lower rating under current thresholds.

Tonnage nomenclature

The convention in Indian model numbers of encoding capacity as a number, usually kW of cooling or a marketing code, rather than as BTU hundreds as in the US. This is why decoding differs by manufacturer.

Turbo mode

A setting running the unit at maximum output to cool a room quickly. Useful briefly, but leaving it on defeats the efficiency advantage of an inverter compressor.

Airflow & ducts

Air balancing

Adjusting dampers so each room receives the airflow its load calls for. Skipped on most residential installs, and the usual reason one room never gets cold.

CFM (airflow)

Cubic feet per minute of air moved by the system — roughly 400 CFM per ton in residential cooling.

CFM per ton

A rule of thumb of roughly 400 CFM per ton of capacity. Lower airflow shifts output toward moisture removal, higher airflow toward temperature drop.

Damper

An adjustable plate that throttles airflow in a duct, used for balancing or for zoning.

Duct leakage

Conditioned air escaping the duct system, typically tested as a percentage of system airflow. Leakage into an attic wastes the cooling entirely.

Equivalent length

The straight duct length that would produce the same resistance as a fitting. Elbows and takeoffs can each add the equivalent of many feet of straight duct.

External static pressure (ESP)

The pressure the blower works against, measured across the air handler. Above the rated value, airflow drops and capacity falls with it.

Face velocity

Air speed at a grille or coil face. High face velocity at a supply register is what people register as a draught.

Flex duct

Insulated flexible duct, quick to install but with far higher resistance than rigid metal, especially when compressed or sharply bent.

Friction rate

The static pressure a duct design is allowed to lose per unit length, the starting input for Manual D duct sizing.

Grille, register and diffuser

Grilles cover an opening, registers add an adjustable damper, diffusers shape the airflow pattern. The terms are often used loosely but describe different components.

Plenum

A sealed chamber at the air handler where supply or return air collects before entering the duct branches.

Return air

Air drawn back to the air handler. Undersized returns are a very common cause of poor airflow and high static pressure.

Short-cycling

When an oversized AC cools so fast it shuts off within minutes, hurting dehumidification and wearing the compressor. See the oversizing guide.

Static pressure (TESP)

Total External Static Pressure — the resistance the blower pushes against (ducts, filter, coil); high values choke airflow.

Supply air

Conditioned air delivered into the space. Volume is set by the room-by-room load, not divided evenly between rooms.

Throw

How far a diffuser projects air into the room before the stream slows. Too short and the far side of the room stays warm.

Trunk and branch

A duct layout with a main trunk feeding smaller branches to each register. The most common residential arrangement.

Equipment

Accumulator

A reservoir on the suction line that prevents liquid refrigerant reaching the compressor. Standard on heat pumps because reversal can return liquid.

Air handler (AHU)

The indoor cabinet containing the blower, evaporator coil and filter in a ducted system. It moves and conditions air but produces no cooling of its own.

Anti-corrosion coating

A protective coating on the outdoor coil, sold as blue fin or gold fin. Worth having in coastal and industrial areas where salt or pollutants attack bare aluminium.

Auxiliary heat

Electric resistance or gas heat that supplements a heat pump below its balance point. Far more expensive to run than the heat pump itself.

Balance point

The outdoor temperature at which a heat pump's output exactly matches the building's heat loss. Below it, supplementary heat is needed.

Cassette AC

An indoor unit recessed into a false ceiling, blowing from multiple sides. Common in Indian commercial spaces where a wall-mounted head would not throw far enough.

Compressor

The pump that compresses refrigerant gas and drives the refrigeration cycle; the most expensive component to replace.

Condensate pump

A small pump lifting condensate to a drain when gravity drainage is not available. A common failure point, and the usual cause of water appearing under an indoor unit.

Condenser

The outdoor coil that rejects heat from the refrigerant to outside air.

Contactor

The electrically operated switch that starts the compressor when the thermostat calls for cooling. Pitted contacts are a frequent cause of a unit that hums but will not start.

Convertible modes

A feature on many Indian split units letting the user cap the compressor at a fraction of rated capacity, marketed as convertible tonnage. It reduces output, not the unit's actual rating.

Crankcase heater

A small heater keeping compressor oil warm so refrigerant does not dissolve into it while off. Why manufacturers ask for power to be on some hours before first start.

Defrost cycle

A periodic reversal that melts frost off the outdoor coil in heating mode. Brief, normal, and the reason a heat pump sometimes blows cool air in winter.

Drain pan

The tray under the evaporator coil that catches condensate. A blocked pan or drain is the first thing to check on a leaking indoor unit.

Dual fuel system

A heat pump paired with a gas furnace, switching to gas when that becomes cheaper than electric heat. Requires a controller aware of both fuel prices.

Ducted split

A split system feeding concealed ducts, giving a single system for multiple rooms without visible indoor units. Usual choice for larger Indian homes above the practical limit for per-room splits.

Ductless mini-split

A split system where the indoor unit blows directly into the room instead of into ducts. Efficient because it avoids duct losses, and the usual choice for adding cooling to one room.

Evaporator

The indoor coil where cold refrigerant absorbs heat from room air.

Filter drier

A component in the liquid line that traps moisture and debris. Replaced whenever the refrigerant circuit is opened.

Heat pump

An air conditioner that can reverse, providing heating as well as cooling. Sizing must satisfy both loads, and the cooling load usually governs in warm climates.

Hi-wall split

The wall-mounted indoor head familiar from Indian residential installations, mounted high on the wall so cool air falls across the room.

Inverter (variable-speed)

A compressor that modulates its speed to match the load instead of cycling fully on and off; steadier temperatures and better efficiency. See inverter vs non-inverter.

Line set

The insulated pair of copper refrigerant lines connecting indoor and outdoor units. Length affects performance, and long runs need a charge adjustment.

Multi-split

One outdoor unit serving several indoor heads on a shared refrigerant circuit. Cheaper on outdoor space than separate systems, but the heads cannot heat and cool simultaneously.

Packaged unit

A single cabinet holding compressor, condenser, coil and blower, usually mounted on a roof or slab. Common in commercial buildings and in some US regions for homes.

Reversing valve

The valve that lets a heat pump swap refrigerant flow to heat in winter and cool in summer.

Run capacitor

A component supplying the phase shift a single-phase motor needs to keep running. A failed capacitor typically presents as a fan that will not spin or a compressor that hums and trips.

SACC

Seasonally Adjusted Cooling Capacity — the honest rating for a portable AC, typically 50–60% of the box BTU. See the portable calculator.

Service valve

A valve on the outdoor unit allowing gauges to be connected without opening the circuit. The Schrader type is the small spring-loaded port under the cap.

Split system

The standard configuration with a compressor and condenser outdoors and an evaporator indoors, joined by refrigerant lines. Nearly all residential air conditioning is a split system of some kind.

VRF / VRV

Variable Refrigerant Flow, a commercial system modulating refrigerant to many indoor units independently. The standard approach for large Indian homes and offices where per-room splits become impractical.

Zoning

Using motorised dampers and multiple thermostats to direct cooling only to the areas that need it.

Efficiency & ratings

AHRI certified reference number

The identifier tying an installed indoor and outdoor unit combination to its tested performance. Efficiency ratings apply to the matched pair, not to either component alone.

Capacity derating

The drop in delivered cooling as outdoor temperature rises above rating conditions. A unit rated at 95°F can lose 10-15% of capacity at 115°F, which matters for sizing in hot climates.

CEER

Combined Energy Efficiency Ratio, the US metric for window and portable units. It includes standby power, so it runs slightly below the older EER for the same machine.

COP (coefficient of performance)

The ratio of useful heat moved to electrical energy consumed; a heat pump with COP 3 delivers 3 units of heat per unit of electricity.

Duty cycle

The proportion of an hour a compressor actually runs. A correctly sized unit on a design day approaches 100%; an oversized one may sit near 30% and cycle repeatedly.

EER / EER2

Efficiency measured at a single hot operating point (95°F outdoor), reflecting peak-day performance.

ENERGY STAR

A US voluntary label awarded to equipment exceeding the federal minimum efficiency by a set margin. It is a threshold, not a ranking, so two labelled units can differ substantially.

EnergyGuide label

The yellow US label showing estimated annual operating cost and where the model sits in its efficiency range. The cost figure assumes a national average electricity rate.

HSPF2

Heating Seasonal Performance Factor (2023 test) — the seasonal heating efficiency of a heat pump.

IEER

Integrated Energy Efficiency Ratio, a part-load weighted efficiency metric used for commercial equipment above the residential SEER2 range.

Life cycle cost

Purchase price plus energy, maintenance and repair over the equipment's life. On air conditioning, energy usually dominates purchase price several times over.

Nominal capacity

The rounded capacity a unit is sold as, such as 3 ton. Actual tested capacity at rating conditions is usually a few percent either side.

Payback period

The time for efficiency savings to repay the extra purchase cost of a higher-rated unit. It shortens with electricity tariff and running hours, which is why the calculation differs sharply between markets.

SEER / SEER2

Seasonal Energy Efficiency Ratio — average cooling efficiency over a season; SEER2 is the tougher post-2023 US test. See SEER vs SEER2.

Standby power

Power drawn while the unit is off but plugged in, for the remote receiver and control board. Small per hour, but continuous across a year.

Total vs sensible capacity

Total capacity is all the heat removed; sensible capacity is only the part that lowers air temperature. The gap is the moisture removal, and it shrinks as a unit is oversized.

Electrical

Dedicated circuit

A circuit serving only the air conditioner. Required for most units above the smallest window sizes, since compressor inrush would trip a shared circuit.

Inrush current

The brief current surge at start-up. Inverter units have far lower inrush because they ramp the compressor up rather than switching it on.

LRA (locked rotor amps)

The current a compressor draws at the instant of starting, several times its running current. It sets the breaker and wire sizing, not the running load.

MCA & MOCP

Minimum Circuit Ampacity and Maximum Overcurrent Protection — the nameplate figures that set wire and breaker sizing for an AC.

MCB

Miniature Circuit Breaker, the standard overcurrent device in Indian and European installations. Sized from the unit's nameplate rather than from its running current.

Power factor

The ratio of useful power to apparent power drawn. Poor power factor raises current for the same work, which matters for cable and breaker sizing on larger installations.

RCCB

Residual Current Circuit Breaker, which trips on earth leakage to protect people rather than equipment. Distinct from the MCB and does not replace it.

RLA (rated load amps)

The current the compressor draws in normal operation at rating conditions. Printed on the nameplate alongside LRA.

Sanctioned load

The maximum load an Indian electricity connection is contracted to supply, in kW. Adding air conditioning can exceed it, requiring an application to raise the sanction rather than just a new breaker.

Three-phase supply

A supply with three live conductors, used for larger equipment. Above roughly 3 tons in India and on most commercial equipment, three-phase is the normal connection.

Voltage drop

The loss along a cable run under load. Long runs to an outdoor unit need a larger conductor than the current alone would suggest.

Voltage stabilizer

A device correcting supply voltage swings before they reach the unit. Widely used in India where grid voltage varies; many modern inverter units have a built-in range and do not need one.

Wire gauge

Conductor size, given in AWG in the US and square millimetres in India. Undersized wire on a long run causes voltage drop that shortens compressor life.

Refrigerant

A2L refrigerant

A classification for refrigerants that are mildly flammable but low in toxicity, including R-32 and R-454B. Installation requires charge limits by room volume and A2L-rated tools.

Evacuation

Pulling the system to a deep vacuum before charging, to remove air and moisture. Measured with a micron gauge, since a compound gauge cannot resolve the range that matters.

Flare fitting

A mechanical joint formed by flaring the copper tube against a fitting, standard on mini-splits and Indian splits. Torque matters: over-tightening cracks the flare and causes slow leaks.

Gas top-up

Adding refrigerant to a system that has lost charge. A system that needs regular top-ups has a leak, and repeated topping up without leak repair is a maintenance failure rather than a service.

GWP (global warming potential)

How much a refrigerant contributes to warming relative to carbon dioxide over 100 years. Regulation is progressively pushing the industry toward lower-GWP options.

Line set length correction

A charge adjustment for refrigerant lines longer than the factory-charged length. Skipping it leaves a long-run installation undercharged.

Nitrogen purge

Flowing dry nitrogen through lines while brazing so the copper interior does not oxidise. Omitting it leaves scale that later blocks the metering device.

R-410A, R-32, R-454B

Refrigerants: R-410A is being phased out for lower global-warming R-32 and R-454B in new US equipment from 2025 (India already uses R-32).

Refrigerant charge

The mass of refrigerant in the system. Both overcharge and undercharge cut capacity and efficiency, and charge is the single most common installation fault.

Refrigerant glide

The temperature spread across evaporation or condensation in a blended refrigerant. Blends with significant glide need superheat and subcooling measured against the correct dew and bubble points.

Retrofit

Changing a system to a different refrigerant, which may require new oil, metering device or components. Rarely economic on residential equipment.

Subcooling

How far liquid refrigerant is cooled below its condensing temperature; a key charging target on TXV systems.

Superheat

How far refrigerant gas is warmed above its boiling point leaving the coil; monitored to protect the compressor.

TXV (thermostatic expansion valve)

A metering device that varies refrigerant flow to hold correct superheat across changing conditions.

Zeotropic blend

A refrigerant mixture whose components evaporate at different temperatures, producing glide. Must be charged as a liquid so the composition stays correct.