Home / Tons ↔ kW & BTU ↔ Watts
Instant converter

Tons to kW & BTU to Watts Converter

Built by Murugan Vellaichamy, Sri Murugan Systems · sources checked November 2026 · how the numbers work

kW (cooling) = tons × 3.517; tons = kW ÷ 3.517. 1.5 tons = 5.28 kW of cooling, but at SEER2 14.3 the AC draws about 1.26 kW from the wall, roughly a quarter of that. Type in either box.

⇄
⇄

1 BTU/h = 0.29307 W, so watts = BTU/h × 0.29307 and BTU/h = watts × 3.412. These are cooling (thermal) watts; the electricity the AC draws is in the table below.

Tons, kW, watts and power draw

The first four columns are cooling capacity. The power-draw column is the average electricity the unit uses while cooling, which is set by its efficiency rating. That figure, not the cooling kW, is what shows up on the bill.

TonsBTU/hrkW (cooling)Watts (cooling)Refrigeration HPPower draw, US (SEER2 14.3)Power draw, India 5★ (ISEER 5.75)
0.759,0002.642,6383.50.63 kW0.46 kW
112,0003.523,5174.70.84 kW0.61 kW
1.518,0005.285,2757.11.26 kW0.92 kW
224,0007.037,0349.41.68 kW1.22 kW
2.530,0008.798,79211.82.10 kW1.53 kW
336,00010.5510,55114.22.52 kW1.83 kW
3.542,00012.3112,30916.52.94 kW2.14 kW
448,00014.0714,06718.93.36 kW2.45 kW
560,00017.5917,58423.64.20 kW3.06 kW

Power draw = BTU/hr ÷ SEER2 ÷ 1,000 (US, at SEER2 14.3: the federal minimum for split ACs under 45,000 BTU/h in the Southeast and Southwest; the national minimum is 13.4, and 13.8 applies in the South at 45,000 BTU/h and up, 10 CFR 430.32(c)), or cooling kW ÷ ISEER (India, at 5.75: the median ISEER of 5-star inverter models on BEE’s register, read 5 Nov 2026). These are seasonal averages, not startup or peak draw. Refrigeration HP uses 1 ton = 4.72 HP. For running cost use the bill calculator; for running amps and the nameplate wire and breaker rules, see the ampere calculator.

Where this conversion shows up

AC capacity is written three ways depending on who is talking: US equipment and Manual J reports use BTU/hr, Indian ACs are sold by tons, and many spec sheets quote thermal kilowatts. Spec sheets for the same unit frequently mix all three, which is why a 1.5-ton split, an 18,000 BTU window unit and a 5.3 kW cassette are the same amount of cooling. Keep thermal output separate from electrical draw: a unit's cooling kW divided by its power consumption is SEER2 ÷ 3.412 (about 3.9 at the 13.4 SEER2 federal minimum) or its ISEER — the bill calculator handles that side.

FAQ

How do I convert tons to kW?

Multiply tons by 3.517. A 1.5 ton AC is 5.28 kW of cooling and a 2 ton AC is 7.03 kW. To go from kW to tons, divide by 3.517.

How many watts does a 1.5 ton AC use?

About 1,259 W of electricity at SEER2 14.3 (the Southeast/Southwest federal minimum; the national minimum is 13.4 SEER2), or about 917 W for an Indian 5-star inverter (ISEER 5.75, the median of 5-star models on BEE’s register). Its cooling output is 5,275 W; the two numbers are different things.

What is the difference between cooling kW and electrical kW?

Cooling kW is the heat the AC removes. Electrical kW is the power it draws to do that. The ratio between them is set by the efficiency rating: SEER2 ÷ 3.412 for US units (about 3.9 at the 13.4 SEER2 federal minimum), or the ISEER figure itself for Indian units. Electrical kW is cooling kW divided by that ratio.

How many watts is 12,000 BTU?

About 3,517 watts of cooling (12,000 × 0.293). That is heat removed, not electricity used: a 12,000 BTU/h system at SEER2 14.3 (the Southeast/Southwest federal minimum) draws roughly 839 watts from the wall.

How do I convert BTU to watts?

Multiply BTU per hour by 0.293 to get watts, or divide watts by 0.293 (multiply by 3.412) to get BTU per hour. Both converters on this page work in either direction.

How many HP is 1 ton of AC?

About 4.72 HP of refrigeration capacity (12,000 BTU/hr). Compressor motor horsepower is a different figure.

Related tools

BTU ↔ tons chart · Tons ↔ kW, HP & electrical draw · Amps & breaker rules · Room size by tonnage

Or skip the conversion and size the room directly with the AC tonnage calculator or BTU calculator.