Home / AC size by area / 1,200 sq ft
Whole-home sizing · cooling, heating, ducts

What Size AC for 1,200 Sq Ft?

1,200 sq ft: 2 ton AC in moderate and mild US climates, 2.5 ton in the warm South and the desert Southwest. In the cool North 1.5 ton is enough. This home’s cooling load ranges from 20,000 BTU/h in the North to 31,100 BTU/h in the hottest climates. Change the county and house below.
Location

Pick your county to fill the 99% heating design temperature from EPA’s ENERGY STAR reference guide, or type your own. Picking your county also sets its 2021 IECC climate zone (see the climate zone map).

Your home
Assumptions used (editable)

Cooling

The county sets the heating numbers (its official winter design temperature). Cooling uses the summer climate you pick, the same model as our area chart.

Your whole system
—AC
Cooling load—
Your quote—
Heat loss—
Gas furnace—
Heat pump—
Airflow—
Main supply duct—
Cooling cost / year—

2 or 2.5 ton for 1,200 sq ft?

Trane’s traditional estimate is 600 sq ft per ton for homes, which gives exactly 2 tons for 1,200 sq ft. That holds in a moderate climate (98% of the cooling load) and a mild one (108%). It stops holding in the warm South, where 2 tons meets only 87%.

Summer climateCooling load (BTU/h)2 ton covers2.5 ton covers3 ton coversSingle-speed fit
Hot31,10077%97%116%2.5 ton
Warm27,70087%108%130%2.5 ton
Moderate24,40098%123%148%2 ton
Mild22,200108%135%162%2 ton
Cool20,000120%150%180%1.5 ton

Percent of a 1,200 sq ft home’s cooling load each size meets. Single-speed target from ENERGY STAR: 90–115%. From the site’s whole-home model (8 ft ceilings, average insulation and sun exposure).

  • 1.5 ton is enough only in the cool North (90%).
  • 2 ton covers moderate and mild summers. In the cool North it is 120% of the load: allowed, but above the recommended band, so 1.5 tons is the better fit there.
  • 2.5 ton is the warm-South size (108%) and the desert size (97%). In a moderate climate it reaches 123%, over the recommended limit for single-speed equipment.
  • 3 ton is above ENERGY STAR’s recommended range for a single-speed system in every band; even in the hottest (116%) it is just over the recommended 115%, though inside the 130% ENERGY STAR allows. A variable-speed 3-ton unit is acceptable in the hot and warm bands.

The calculator picks the row from the first three digits of your ZIP code. At 1,200 sq ft, 2 ton fits the moderate band (Los Angeles and Nashville), a load of 24,400 BTU/h; it also fits the mild band (22,200 BTU/h). Move to the warm band (Birmingham and Oklahoma City) and it is 27,700 BTU/h, of which 2 ton covers 87%; that calls for 2.5 ton. The hot band (Phoenix and Tampa) pushes the load to 31,100 BTU/h, of which 2 ton covers 77%, which means 2.5 ton. Go north to the cool band (Fargo and Madison) and it drops to 20,000 BTU/h (2 ton would be 120% of it): 1.5 ton does the job. A metro on a band edge can sit in either band, so run your own ZIP above.

Worked example: a slab ranch in Phoenix

A 1,200 sq ft single-story ranch on a slab in Maricopa County, Arizona, with 8 ft ceilings and typical 1990s–2000s insulation. Phoenix has the most cooling degree days of any city on this site (4,765 a year), and ENERGY STAR’s 1% cooling design temperature for the county is 111°F.

StepFor this house
1. Summer climatePhoenix ZIP codes (850, 852–853) sit in the calculator’s 850–857 block, which falls in the calculator’s Zone 1 (hot); the moderate-climate figure is multiplied by 28/22
2. Cooling load24,400 × 28/22 = 31,100 BTU/h
3. Sizes2 ton: 77%, too small · 2.5 ton: 97%, recommended · 3 ton: 116%, oversized for single-speed
4. Design temperaturesMaricopa County (ENERGY STAR): 111°F summer (1%), 24°F winter (99%). Heat loss 14,900 BTU/h
5. ElectricityArizona residential average 15.1¢/kWh in August 2026. Our labelled assumption of 2,400 full-load hours gives about 5,035 kWh (≈ $758) at 14.3 SEER2 and 4,580 kWh (≈ $689) at the 15.7 SEER2 certified average

Result: 2.5 tons. It meets 97% of the load, inside the recommended band, though near its lower end. The size step below (2 tons, 77%) is far too small, and 3 tons (116%) would be oversized for a single-speed unit.

Winter is mild (24°F design temperature) and the heat loss is about 14,900 BTU/h, A 2.5-ton heat pump delivers about 25,100 BTU/h at 24°F, so it heats the house without backup heat.

Arizona, California, Nevada and New Mexico: the EER2 rule

SEER2 is a seasonal average. EER2 is the efficiency at one hot condition, 95°F outdoors, which matters more where afternoons run past 105°F. Federal rules add an EER2 floor for split-system ACs installed in the Southwest since January 1, 2023:

  • Under 45,000 BTU/h (every size a 1,200 sq ft home needs): at least 14.3 SEER2 and 11.7 EER2.
  • If the system is rated 15.2 SEER2 or higher, the EER2 floor drops to 9.8.
  • An outdoor unit with any certified combination below the standard cannot be installed in those four states.

Low-desert counties have some of the highest summer design temperatures in ENERGY STAR’s county guide, which is why the same floor area needs more capacity there:

CountySummer design (1%)Winter design (99%)
Maricopa County, Arizona111°F24°F
Pima County, Arizona109°F22°F
Yuma County, Arizona112°F27°F
Clark County, Nevada116°F17°F
Riverside County, California112°F11°F
Imperial County, California110°F33°F
Kern County, California108°F21°F

ENERGY STAR Design Temperature Limit Reference Guide (2019): the 1% cooling and 99% heating design temperatures set for each county.

The EER2 floor applies to air conditioners. Certified 2.5-ton heat pumps in ENERGY STAR’s list have EER2 ratings of 9.1–13.5. Ask for the EER2 on the quote, not only the SEER2; at a 111°F design afternoon it is the closer guide to how the unit performs.

Supply is not a constraint at these sizes: ENERGY STAR lists 76,856 certified ducted heat pump combinations around 2 tons (57% variable-speed) and 14,384 around 2.5 tons.

Where 2 tons stops being enough

Between Charlotte (1,769 cooling degree days) and Dallas–Fort Worth (2,824), a 1,200 sq ft home moves from 2 tons to 2.5 tons. NOAA’s 1991–2020 normals give the degree days below.

Calculator climateExample cities (cooling degree days)Load (BTU/h)Single-speedVariable-speed
Zone 1 — HotPhoenix, AZ (4,765); Las Vegas, NV (3,720)31,1002.5 ton2.5–3 ton
Zone 2 — WarmDallas-Fort Worth, TX (2,824)27,7002.5 ton2.5–3 ton
Zone 3 — ModerateCharlotte, NC (1,769)24,4002 ton2–2.5 ton
Zone 4 — MildNew York (Central Park), NY (1,222); Chicago, IL (1,003)22,2002 ton2 ton
Zone 5 — CoolMinneapolis, MN (830)20,0001.5 ton1.5–2 ton

Annual cooling degree days, NOAA normals 1991–2020, base 65°F.

ZIP codes map to these summer climates in the calculator above; official county zones are on the climate zone map.

Cooling-only central ACs at 2, 2.5 and 3 tons

ENERGY STAR stopped certifying central ACs on February 1, 2026; the DOE certification database still lists every one sold, so the cooling-only options for 1,200 sq ft come from there.

SizeShare of a 1,200 sq ft home’s moderate-band loadCertified combinationsOutdoor modelsSEER2 rangeMeet the Southeast/Southwest SEER2 floor (SEER2 only)17 SEER2 or moreRated coil-only
2 ton98%460,83794613.4–26 (avg 15.6)90%18%4%
2.5 ton123%377,26365213.4–23.4 (avg 15.0)86%0.4%4%
3 ton148%586,23292213.4–23.5 (avg 15.4)89%8%3%

DOE certification database, split-system ACs, read 2026-11-05; each size is a band of certified capacity (2 ton = 22,000–25,999 BTU/h). Regional SEER2 floor: 14.3 SEER2 under 45,000 BTU/h, 13.8 at 45,000 BTU/h and above (10 CFR 430.32(c)(6)). The Southeast/Southwest column counts that SEER2 floor only. The Southwest also sets an EER2 minimum (11.7, or 9.8 at 15.2 SEER2 or more; 11.2 or 9.8 at 45,000 BTU/h and above), which the column does not check.

For the 2-ton unit a 1,200 sq ft home needs in a moderate summer, DOE lists 460,837 combinations built on 946 outdoor models. 10% of them are below the 14.3 SEER2 floor for the Southeast and Southwest (Texas, Florida, Georgia, Arizona and California among them), so there, check the rating on the quote.

DOE measures these ratings on a test rig, not through your ductwork, so a leaky system delivers less than the label. Of the two sizes this page weighs, 2 tons is also far better supplied with efficient units (18% at 17 SEER2 or more) than 2.5 (0.4%).

Homes of 1,000–1,499 sq ft

EIA’s housing survey counts 24.5 million air-conditioned homes in this size band. In 18% of them the AC is simply switched on and off as needed rather than left at a setpoint, and 19% run a main unit that is 15 or more years old.

1,100 and 1,300 sq ft

Homes of 1,100 and 1,300 sq ft are covered here as well.

AreaLoad, moderate (BTU/h)Load, warm South (BTU/h)Moderate-climate sizeBTU per sq ft
1,100 sq ft22,70025,8002 ton20.6
1,200 sq ft24,40027,7002 ton20.3
1,300 sq ft26,10029,7002–2.5 ton20.1

Loads from this site’s sizing model (how it works): planning estimates, not a room-by-room load calculation.

At 1,300 sq ft a moderate climate sits between sizes: 2 tons meets 92% and 2.5 tons 115%, so both are inside the recommended band. For smaller homes see 1,000 sq ft (2 tons moderate); for larger, 1,500 sq ft (2.5 tons).

Next steps

FAQ

Is a 2 ton AC enough for 1,200 sq ft?

In moderate, mild and cool climates, yes (98%, 108% and 120% of the cooling load). In the warm South it meets 87% and in the desert 77%; use 2.5 tons there.

Is 2.5 ton too big for 1,200 sq ft?

Only outside the hot regions. It is the right size in the warm South (108%) and the desert (97%), but 123% of the load in a moderate climate.

How many tons of AC for 1,100 sq ft?

About 22,700 BTU/h in a moderate climate, so 2 tons (106% of the load). In the warm South the load is about 25,800 BTU/h.

What size AC for 1,300 sq ft?

About 26,100 BTU/h in a moderate climate: 2 tons (92%) or 2.5 tons (115%) both fit. In the warm South, about 29,700 BTU/h calls for 2.5 tons.

What is the formula for AC tonnage?

Tons = cooling load (BTU/h) ÷ 12,000. A 1,200 sq ft home in a moderate climate has a load of about 24,400 BTU/h, which is 2.0 tons.

How many square feet does a 1-ton AC cool?

It depends on the climate, because the load per square foot does. At this home size our model works out to about one ton per 460 sq ft in the hottest areas, 590 sq ft in a moderate climate and 720 sq ft in the cool North. That is why 1,200 sq ft lands on 2 tons in one place and 2.5 in another.

What SEER2 and EER2 do I need in Arizona?

A new split-system AC under 45,000 BTU/h must be at least 14.3 SEER2 and 11.7 EER2, or 9.8 EER2 if it is rated 15.2 SEER2 or higher. The same applies in California, Nevada and New Mexico.

How much does it cost to run a 2.5-ton AC in Phoenix?

At Arizona’s 15.1¢/kWh and 2,400 full-load hours (our labelled assumption), about $758 a year at 14.3 SEER2 and $689 at 15.7 SEER2. Enter your own hours in the calculator.

How do I tell the tonnage of my AC from its model number?

Look on the outdoor unit’s data plate. Most US brands put the size in the model number as thousands of BTU/h, a code divisible by 6: 18 = 1.5 ton, 24 = 2, 30 = 2.5, 36 = 3. On a Carrier it is characters 7–8: a 24ACC636 reads 36, so 3 tons, and a 24 in that place means 2 tons, the moderate-climate size for 1,200 sq ft. The model number decoder reads Carrier and 12 other US brands.

Sources used on this page

actonnagecalc.com is not affiliated with, or endorsed by, the U.S. EPA, ENERGY STAR®, DOE or the ICC. Their publications are cited as sources.

Updated 6 November 2026